Every few minutes, the control room at the National Energy System Operator (NESO) adjusts Great Britain’s power system to keep supply and demand in balance. It does this through the Balancing Mechanism, where generators and batteries offer to raise or lower their output at a price. In principle, the control room should take the cheapest offers that solve the problem. In practice, batteries are frequently passed over for more expensive gas plants, which the industry calls skips.
What is a skip?
A skip happens when the control room rejects a cheaper offer and accepts a more expensive one for reasons other than price. An offer that would have been the actual economic choice is called in-merit, and when the control room passes it over for a pricier option, the offer is skipped.
UK – Burnham’s first budget ends VAT relief for home solar
Batteries, which now provide a growing share of the grid’s balancing capacity, have borne the brunt of the problem. Storage operators first raised the issue in 2023, when their trade body reported an average skip rate of 80 percent. NESO has since published its own skip-rate methodology and reports on its progress every few months.
How bad is it in reality?
That depends on how the skips are measured. NESO’s own figures show battery skip rates falling from an average of 49 percent in the first half of 2025 to 38 percent in the first half of 2026, which suggests at first glance that the situation is improving.
Modo Energy, which tracks battery revenues, measures something slightly different: the share of in-merit battery volume that NESO actually uses. By that measure, the picture has worsened. In October, NESO took up 7 percent of the battery power offered at in-merit prices, down from 15 percent a year earlier, and 11 percent of in-merit bids to absorb power, down from 21 percent. For every 1 MWh of battery power offered below the price of gas that it accepted, it left 11 MWh unused.
The two sets of figures are not necessarily in conflict. Batteries delivered 427 GWh through the Balancing Mechanism in October, the highest monthly volume in 13 months, but the battery fleet, which currently stands at around 8.5 GW, is growing faster than the control room is calling on battery power.
So why does it happen?
For the control room, a gas plant is easy to plan around: once it‘s up and running, it can keep going for hours. A battery can only run until it is empty, and until recently, the control room had no reliable way of knowing how much energy each battery had remaining. Faced with this lack of information, operators often chose the predictable option.
UK – along the River Trent, solar inherits the grid from coal
Battery dispatch also tends to come in short bursts. Between January and October, three-quarters of accepted battery offer energy came from instructions lasting ten minutes or less. In regions where generation regularly exceeds what the grid can carry, such as Scotland, batteries are often called in to ease bottlenecks, whatever their price. There, 59 percent of battery bids were flagged as system actions, against 1 percent in England.
The cost of skipping batteries
When a cheap battery offer is skipped, a gas plant usually runs instead, raising balancing costs that are passed on to consumers. When a battery bid to absorb power is skipped, more surplus wind goes to waste. and battery owners lose revenue that they would otherwise earn.
The amounts are disputed, but the direction is clear. Modo estimates that batteries saved consumers more than £23 million in balancing costs between December 2024 and late 2025, and that Scottish batteries saved around £30 million between December 2024 and April 2026, despite charging during grid constraints. NESO is working on its own estimate of what skips cost.
What‘s changing?
NESO’s Open Balancing Platform, introduced in December 2023, allows the control room to instruct many small units at once, and the volume of battery power it uses has risen more than tenfold since then.
The latest step is a grid code change known as GC0166. This requires batteries to tell the control room the maximum energy they can deliver or absorb at any moment, known as the Maximum Delivery Offer and Maximum Delivery Bid. By the deadline of 5 November, 184 of 196 battery units, or 7.7 of 8.5 GW, were sending this data. According to Modo, batteries already submitting the new data received 71 percent more offer volume and 23 percent more bid volume per MW than those that were not. They were called on more often, but for around two minutes less each time.
UK – Bridgwater factory to carry country’s largest solar roof
NESO is also considering limits on how storage behaves behind grid constraints, a proposal that battery owners argue would do more harm than good for consumers.
Will the new data help?
November is the first full month in which almost every battery on the grid has sent its data to the control room, so December’s figures will show whether GC0166 is making a difference. Without a clear improvement, pressure will grow for a deeper reform of dispatch, a system that battery owners say has not kept up with how the grid has changed. (TF)